actuator air Cylinder Solenoid Valve Transmitter SMC Parker Festo Schrader Miller Bosch Rexroth CKD Knorr Milwaukee Vickers Taiyo Numatics Mosier Allen Humphrey Koganei
Categories

Buschjost solenoid valve with differential pressure Norgren solenoid valve Series 82680/82470

2/2-way valves DN 8 to DN 25
For hot water and steam
Indirectly solenoid actuated
Diaphragm valves
Internal thread G 1/4 to G 1 or 1/4 NPT to 1 NPT
Operating pressure 0.1 to 10 bar
Description (standard valve)
Solenoid valve for hot water and steam
Switching function:  normally closed
Flow direction:  determined
Differential pressure:  0.1 bar required
Fluid temperature:  0 !aC up to max. +150 !
Ambient temperature:  ¨C10 !aC up to max. +60
Mounting position:  as required, preferably with  
solenoid vertical on top
Material
Body:  Brass (CW617N)
Seat seal:  HNBR
Internal parts:  Stainless steel, brass
For contaminated fluids insertion of a strainer is recommended (see B - accessories).
FeaturesHigh flow rateDamped operation Functional compact design Solenoid interchangeable without tools (c)

Characteristic data
Valves
Part Number Nominal Dia- Operating pres-
Connection size Valve length kv-value **
Weight
Solenoid 1 or 2 meter  sure *
3
(mm) max. (bar) (Base m /h) (kg)
(mm) min. (bar)
8247000.9101 G 1/4
8 60 0.1 10 1.70 0.47
8268000.9101 1/4 NPT
8247100.9101 G 3/8
10 60 0.1 10 2.70 0.45
8268100.9101 3/8 NPT
8247200.9101 G 1/2
12 67 0.1 10 3.40 0.50
8268200.9101 1/2 NPT
8247300.9101 G 3/4
20 80 0.1 10 5.50 0.65
8268300.9101 3/4 NPT
2
*  for gases and liquid fluids up to 25 mm /s (cSt) State voltage [V] and frequency [Hz
** Cv-value (US) !O kv-value x 1.
Further options (Valves)Solenoid 9101
XXXXX01.XXXX  Normally open (NO)Standard voltage
On request  Further versions
DC 1 AC 2
60 Hz
50 Hz
24 V 24 V -
 -  110 V 120V
 -  230 V 220 V
Design acc. to DIN VDE 0580
Voltage range  !à10
100 % duty cycle
Protection class acc. to EN 60529 IP65
Socket Form A acc. to DIN EN 175301-803 (included)
AC with rectifier plug
Power Consumption
According to DIN VDE 0580 at coil temperature of +20 !aC. In
operation the power consumption of the solenoid decreases
by approx. 30 %.
AC 2
Solenoid DC 1
Inrush Holding
9101 * 8 W 15 VA 12 VA

Write a review